登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给排水科学与工程 > 正文

南京某行政办公楼给水排水工程设计毕业论文

 2022-01-31 21:51:31  

论文总字数:39587字

摘 要

给水系统分区供水,从市政管网上接一根DN100的引入管,地上二层为市政管网直供,三至十层采用无负压变频供水设备加压供水,十一至十八层采用无负压变频供水设备加压供水并预留DN65给水管供空调机房用水。消防水池采用钢筋混凝土结构,置于地下室泵房外侧,有效容积864立方。建筑室内排水采用污、废水合流制,室外排水采用污废合流制,排入检查井后,经化粪池处理再排入市政污水管。卫生间采用多设立管形式,采用专用通气立管。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑采用内排水,选择重力半有压流系统,雨水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为一类高层建筑,室外消火栓用水量30L/s,室内消火栓用水量40L/s,火灾延续时间3h。消火栓充实水柱高度12m,水龙带长度25m,水枪喷嘴流量5.16L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量40L/s。报警阀设于地下室泵房内,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分3个区。选用箱泵一体化消防增压稳压设备(包含18立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统

Abstract

The water supply system is zoned for water supply. A DN100 inlet pipe is connected from the municipal pipe network. The ground floor is directly supplied by the municipal pipe network. No pressure vacuum water supply equipment is used for pressure supply on the third floor to the tenth floor. Negative pressure frequency conversion water supply equipment pressurized water supply and set aside DN65 water supply pipe for air conditioning engine room water. The fire water tank adopts a reinforced concrete structure and is placed outside the basement pump room. The effective volume is 864 cubic meters. The internal drainage of the building adopts a combined system of sewage and waste water, and the outdoor drainage adopts a combined waste and waste system. After being discharged into the inspection well, it is treated in the septic tank and discharged into the municipal sewage pipe. The toilet uses multiple tubes to form a special vented riser. The drainage of the basement is drained to the sump through the drainage ditch and lifted by the submersible sewage pump to the inspection well. The building uses internal drainage, and a gravity semi-pressure flow system is selected. The rainwater is collected by the roof rainwater bucket and discharged from the rainwater pipe to the inspection well.

According to the specifications, the building is a type of high-rise building with outdoor fire hydrant water consumption of 30 L/s, indoor fire hydrant water consumption of 40 L/s, and fire duration of 3 h. The fire hydrants were enriched with a water column height of 12m, a hose length of 25m, a nozzle flow rate of 5.16L/s, and a fire riser pipe diameter of DN100. One test fire hydrant is provided on the roof layer, and each indoor fire hydrant box is provided with a button for remotely starting the fire pump.

The building uses a wet sprinkler system with a design flow of 40 L/s. The alarm valve is located in the pump room in the basement. Each floor is provided with a flow indicator, an end test device and a signal valve. The signals are sent to the fire control center for processing. The project's automatic sprinkler system is divided into 3 zones. Use box-pump integrated fire-fighting pressurization and voltage stabilization equipment (including 18 cubic meters of fire water tanks) to store fires in the initial stage of 10 min. Automatic sprinkler system and indoor hydrant system water consumption. Initially, fire extinguishers are supplied by the tanks. Fire extinguishers in the basement are fire-fighting pumps and sprays. Dripping pump water supply.

Keywords: water supply system, drainage system, hydrant system, automatic sprinkler system, rainwater system

南京某行政办公楼给排水设计任务书

一、工程概况

南京某行政办公楼主体建筑为十八层,地下一层为车库,地上一到十八层均为办公场所,每层建筑面积900~1200m2,建筑总高度67.20m。

  1. 给水水源

本建筑以城市给水管网作为水源,从西北侧的市政管网取水,供水水压为0.25MPa。室外消防给水可通过市政管网提供。

(2)排水条件

建筑采用合流排水体制,污水可直接排入城市排水管网集中送至污水处理厂。

二、设计依据

1.建筑给水排水设计规范GBJ50015-2003(2009年版);

2.建筑设计防火规范GB50016-2006(2006年版);

3.高层民用建筑设计防火规范GB50045-95(2005版);

4.给排水制图标准GB/T50106-2001

5.自动喷水灭火系统设计规范GB50084-2001(2005版);

6.有关文件及各工程提供的资料,包括:8张平面图,4张立面图,1张剖面图。

三、设计内容

本设计应包括生活给水系统、消防系统(包括消火栓系统和自动喷水灭火系统)、生活排水系统、雨水系统。

四、完成的工作量

  1. 设计计算说明书一本,包括如下内容:
    1. 方案的选择和比较;
    2. 给水系统水力计算;
    3. 消火栓系统水力计算;
    4. 喷淋系统水力计算;
    5. 排水系统水力计算;
    6. 主要设备的选型与计算
  2. 图纸
    1. 图纸目录 1 张
    2. 地下一层给排水平面 1 张
    3. 一层给排水平面 1 张
    4. 二层给排水平面 1 张
    5. 三层给排水平面 1 张
    6. 标准层给排水平面 1 张
    7. 九、十四层给排水平面 1 张
    8. 屋顶水箱给排水平面 1 张
    9. 给水系统图 1 张
    10. 消火栓系统图 1 张
    11. 喷淋系统示意图 1 张
    12. 排水系统图 1 张
    13. 泵房工艺图 1-2 张
    14. 设计总说明(含设备材料表) 1 张
    15. 给排水详图 1-3 张

合 计 15-18张

五、设计进度计划

(1)准备各种规范、手册,熟悉设计资料 1天

(2)给水方式调研 5天

(3)完成调研报告 5天

(4)确定给水方案 3天

(5)做草图、进行水力计算 14天

(6)做系统图、完成水力计算 10天

(7)整理说明、计算书、设备选型 5天

(8)计算机绘图 15天

(9)答辩准备 3天

(10)答辩 2天

(11)机动

合计 63天

目 录

第一章 设计说明书

一、给水系统 1

1.1给水方案 1

1.1.1方案选择 1

1.1.2方案选择依据 2

1.2给水系统组成 3

1.3给水管道的布置与敷设 3

二、消防系统 5

2.1室内消火栓系统 5

2.1.1室内消火栓系统的选择 5

请支付后下载全文,论文总字数:39587字

您需要先支付 50元 才能查看全部内容!立即支付

微信号:bysjorg

Copyright © 2010-2022 毕业论文网 站点地图