登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给排水科学与工程 > 正文

卫校教学楼给排水设计毕业论文

 2022-03-10 20:22:06  

论文总字数:38399字

摘 要

本设计是南京卫生学校给排水设计,主要包括生活给水系统、消火栓系统、自动喷淋灭火系统、排水系统和屋面雨水排水系统五个系统。

给水系统分区供水,从市政管网上接DN100的引入管,底层层至地上三层为市政管网直供,四至十一层采用无负压变频供水设备加压供水。地下消防水池采用钢筋混凝土结构,置于地下室泵房边,有效容积214立方米。建筑室内排水采用污废合流制,直接排入市政污水管。排水立管采用专用通气立管,部分使用环形通气管。地下室排水经排水沟汇集排至集水坑,经潜污泵提升排至检查井。建筑外排水,选择重力半有压流系统,侧面外排引向室外周围地面散排,雨水经屋面雨水斗收集后排入雨水管。

根据规范,该建筑为二类高层建筑,室外消火栓用水量30L/s,室内消火栓用水量20L/s,火灾延续时间2h。水龙带长度25m,保护半径23m,水枪喷嘴流量5.42L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

本工程的自动喷水灭火系统分竖向分为四个区。该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量16L/s。报警阀设于地下室泵房内,各层均设水流指示器、信号阀和末端试水装置,其信号均送入消防控制中心进行处理。选用消防增压稳压设备(包含有效体积24立方米消防水箱)贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,设于屋顶,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给排水系统、消火栓系统、自动喷水灭火系统、雨水系统

Abstract

This design is the design of water supply and drainage for Nanjing health school. It mainly includes five systems: domestic water supply system, fire hydrant system, automatic sprinkler system, drainage system and roof rainwater drainage system

The water supply system of water supply pipe is connected with the partition, online introduction of DN100 from the municipal pipe, floor to three layers on the ground for the municipal pipe network direct supply, four to eleven non negative pressure water supply equipment pressurized water. Underground fire pool adopts steel reinforced concrete structure in the basement pump room side, effective volume of 214 cubic meters. The indoor use of drainage sewage drainage system, directly into the municipal sewage pipe. Vertical drainage pipe with special ventilation riser, part of the use of annular ventilation tube. The basement drainage drainage ditch pool drained to the sump, the submersible sewage pump up and drained to check well. Outside the building gravity drainage, half pressure flow system, side discharge to outdoor The ground around the scattered row, the roof rainwater rainwater hopper collect back into the rain water pipe.

According to the specification, the building is two tall buildings, outdoor fire hydrant water 30L/s, indoor water hydrant fire duration 20L/s, 2h. hose length is 25m, the radius of protection 23m, water gun nozzle flow 5.42L/s, riser diameter DN100. test on the roof layer a fire hydrant, fire hydrant box are equipped with each distance start the fire pump button.

The system is divided into four zones of vertical automatic sprinkler fire. The construction of this project adopts wet automatic sprinkler system, alarm valve 16L/s. system design flow in the basement pump room, each layer shall be provided with flow indicator and signal valve end testing device, the signals are sent into the fire control center for processing. The fire pressure stabilizing equipment (including the effective volume of 24 cubic meters of water tank) storage early fire sprinkler 10min fire extinguishing system, water, indoor fire hydrant system is arranged in the roof, the early fire from a water tank, the late fire by the fire pump and spray pump water in the basement.

Key words: water supply and drainage system, fire hydrant system, automatic sprinkler system, storm water system

目 录

第一章 设计说明书 3

一、给水系统 3

1.1方案比选 3

1.2室内给水系统的组成 4

1.3给水管道的布置与敷设 4

二、消防系统 5

2.1消火栓系统 5

2.2自动喷水灭火系统 6

三、排水系统 7

3.2排水管道的安装 8

四、雨水系统 8

4.1雨水排水系统的选择 8

4.2雨水排水系统的组成 8

4.3雨水管道的敷设与布置 8

第二章 设计计算书 9

一、给水系统计算 9

1.1用水量计算 10

1.2给水管网水力计算 10

二、 消火栓系统 24

2.1消防水池 24

2.1.1消防水池的设置 24

2.1.2体积计算 24

2.2屋顶消防水箱 25

2.3消火栓保护半径 26

2.4消火栓布置间距 26

2.5消火栓的确定 26

2.7水泵接合器选定 30

2.8消火栓减压计算 30

三、 自喷系统 31

3.1自动喷淋灭火系统的基本数据 31

3.2管道与报警阀布置 31

3.3系统的设计流量 33

3.4水力计算(作用面积法) 37

3. 5 室外消火栓与水泵接合器的选择 41

3.6消防泵房布置与管材选择 41

3.6.1管材 41

3.6.2泵房布置 42

四、排水系统计算 42

4.1确定排水体制 42

4.2排水水力计算 42

4.3地下室排水系统计算 54

4.4化粪池设计计算 55

五、 雨水系统计算 56

5.1暴雨强度公式 57

5.2雨水设计流量公式 57

5.3雨水水力计算表 57

5.5雨水斗 58

5.4排出管计算 58

第一章 设计说明书

一、给水系统

1.1方案比选

南京卫生学校为新建高层建筑,建筑层数:地下一层,地上十一层;建筑总高度为45m,总建筑面积约2.1万平方米,地下室为设备房和停车库;一至十层为教学办公区,十一层为多功能用途区,包括机房、办公室和会议室,并设有中央空调系统。

(1)方案一:高位水箱并联给水

供水系统主要由贮水池、加压水泵、高位水箱和配水管网组成。高位水箱在给水系统中的作用,主要是贮水、调节水量和稳定水压。高位水箱并联给水方式是各分区独立设置水箱和水泵,水泵集中布置在建筑底层和地下室,分别向各区供水。

优点:由于各区是独立的供水系统,供水安全可靠;水箱分散设置,各区水箱容积小,有利于结构设计,运行动力费用经济;水泵集中布置,便于维护管理。

请支付后下载全文,论文总字数:38399字

您需要先支付 50元 才能查看全部内容!立即支付

微信号:bysjorg

Copyright © 2010-2022 毕业论文网 站点地图