某高层住宅建筑给排水设计毕业论文
2022-05-06 20:59:06
论文总字数:20111字
摘 要
本设计一层至地上三层为市政管网直供,四至十二层为变频泵供水的给水方式,十三至十八层为设水泵、水箱供水方式。直供部分从市政给水管网接一根DN70的引入管,另两根DN100的引入管接至地下一层生活水池和消防水池。生活水池和消防水池采用砖砌混凝土结构,置于地下室。排水采用生活污、废水合流制。通气管除一至三层排水外均采用专用通气立管通气。泵房排水槽经汇集排至地下一层污水井,经潜污泵提升排至检查井再经过化粪池处理后排入市政排水管。屋面雨水排放选择重力式雨水系统,雨水经屋面雨水斗收集后由雨水管排至检查井。
根据规范,该建筑为一级耐火等级二类建筑,属中度危险一级。室内消防流量20L/s,室外15L/s。充实水柱取12m,水龙带长度取25m,水枪喷嘴口径19mm,配备DN65水带,水枪喷嘴流量5L/s,消防立管管径为DN100、DN150。在顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。
该建筑采用湿式自动喷淋灭火系统,报警阀设于地下一层,各层均设水流指示器、末端试水装置和信号阀,其信号均送入消防控制中心进行处理。本工程的自动喷水灭火系统分4个区。屋顶水箱为18立方米为消防水箱,贮存10min自动喷水灭火系统、室内消火栓系统用水量。自动喷水灭火系统和消火栓系统的初期灭火由水箱供水,后期供水由地下室的消防水泵和自喷泵供水。
关键词:住宅楼、给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统
Abstract
The design for the municipal level to the ground three direct supply pipe network, four to ten two for the lead pump water supply water way, thirteen to ten eight to set up water pumps, tank water supply. Supplying part from the municipal water supply network connected to an introduction pipe DN70, DN100 introduced another two tubes connected to the ground floor living pond and fire pond. Life and fire water pond using concrete masonry structure, placed in the basement. The use of domestic sewage and drainage, wastewater Combined. Snorkel outside except one to three drainage are using special ventilation riser ventilation.Pumping stations and drainage collection tank through the basement sewage discharged into the wells, the submersible sewage pump discharge to enhance the well and then after checking into the municipal sewer septic tanks. Select gravity roof drainage rainwater system, rain water bucket after the roof rainwater collection pipe to an inspection by a row of wells.
According to the specification, the building was a fire rating II building, is a moderate risk level. Indoor fire flow 20L / s, Outdoor 15L / s. Enrich the water column to take 12m, hose lengths are 25m, gun nozzle diameter 19mm, DN65 with hose, gun nozzle flow 5L / s, fire standpipe diameter is DN100, DN150. In the top set up a test fire hydrant, fire hydrant box each have a remote start the fire pump buttons.
The building wet automatic sprinkler system, alarm valve located in the basement, the layers are set flow indicator, end water apparatus and a signal valve, which signals are sent to the fire control center for processing. Automatic sprinkler system of this project is divided into 4 zones. Rooftop water tanks for the fire to 18 m3 tank, storage 10min sprinkler system, fire hydrant system water. Automatic sprinkler systems and fire hydrant system early water from the tank, the water from the basement of the late fire pumps and pump water from the spray.
Key words:Residential Building, water supply system, drainage system, fire hydrant system, automatic sprinkler system, rainwater systems.
目 录
摘 要 I
Abstract II
第一章 设计任务书 1
一、 工程概况 1
二、设计依据 1
三、 设计内容 1
四、设计要求 2
五、毕业设计进程安排 2
第二章 设计说明书 4
一、给水系统 4
二、排水系统 4
三、雨水系统 5
四、消火栓给水系统 5
五、自动喷淋系统 5
第三章 计算说明书 7
一、给水系统 6
1、设计秒流量计算 6
2、低区生活给水系统水力计算 6
3、中区生活给水系统水力计算 8
4、高区生活给水系统水力计算 10
5、生活贮水池容积计算 12
二、排水系统 12
1、卫生器具排水定额及排水管道设计秒流量公式的确定 12
2、建筑内排水管道计算 13
3、地下室排水系统计算 19
4、汽车库排水系统计算 19
5、消防电梯排水系统计算 19
三、消火栓系统 19
1、室内消火栓系统计算 19
2、室内消火栓系统屋顶增压设施设计 24
3、减压孔板计算 25
4、 水泵接合器设置 25
5、消防水箱 25
6、消防贮水池 26
四、自动喷水灭火系统 27
1、自动喷水灭火给水系统 27
2、喷头的选用与布置 28
3、水力计算 28
五、雨水系统 31
1 、降雨强度的确定 31
2、 雨水立管的布置 31
3、 雨水水力计算 32
六、室外雨水水力计算 32
结束语 33
参考文献 34
致 谢 35
第一章 设计任务书
一、工程概况
请支付后下载全文,论文总字数:20111字