登录

  • 登录
  • 忘记密码?点击找回

注册

  • 获取手机验证码 60
  • 注册

找回密码

  • 获取手机验证码60
  • 找回
毕业论文网 > 毕业论文 > 土木建筑类 > 给水排水工程 > 正文

南京南方宾馆大楼给排水设计毕业论文

 2022-05-02 22:21:23  

论文总字数:38194字

摘 要

给水系统分区供水,宾馆给水从市政管网上接一根DN100的引入管,宾馆建筑二层至四层为市政管网直供,五层至十三层采用水泵水箱给水方式。附属用房给水A二层至五层;附属用房B三层至4层为市政管网直供,以上楼层由宾馆高位水箱供给。消防水池采用钢筋混凝土结构,置于宾馆地下室南侧,有效容积384立方。建筑室内排水采用污、废水合流制,经化粪池处理再排入市政污水管。卫生间采用多设立管形式,采用升顶通气方式。一层废水单排,雨水采用普通外排水经屋面雨水斗收集后由雨水管排至检查井。

根据规范,该建筑为二类高层建筑,室外消火栓用水量20L/s,室内消火栓用水量30L/s,火灾延续时间2h。消火栓充实水柱高度12m,水龙带长度20m,水枪喷嘴流量5.7L/s,消防立管管径为DN100。在屋顶层设试验消火栓一个,每个室内消火栓箱内均设有远距离启动消防泵的按钮。

该建筑采用湿式自动喷水灭火系统,喷淋系统设计流量40L/s。报警阀设于一层泵房内,在每个湿式报警系统的末端设置末端试水装置,其余各层均设试水阀和信号阀,其信号均送入消防控制中心进行处理。选用18立方米消防水箱贮存火灾初期10min自动喷水灭火系统、室内消火栓系统用水量,初期灭火由水箱供水,后期灭火由地下室的消防水泵和喷淋泵供水。

关键词:给水系统、排水系统、消火栓系统、自动喷水灭火系统、雨水系统

Abstract

Water supply system water, from municipal pipe network pick a service pipeDN100,Hotel building floor to four for the municipal pipe network direct supply, five to thirteen water tank using the pump mode. A two-story attached house water supply to five; three to four ancillary buildings B layer Supplying municipal pipe network, supplied by the hotel floor above the high water tank. Fire basin made of reinforced concrete structure built ithe basement on the south side hotel, the effective volume of 384 cubic meters. Architecture Indoor use sewage drainage, wastewater Combined, the septic tank and then discharged into the municipal sewer. Toilet multi-establishment tube form, using or roof ventilation mode. One single row of wastewater, rainwater drainage outside the ordinary roof water bucket after discharge from the rainwater collection pipe to manholes.

According to the specification, the building of two types of high-rise buildings, outdoor fire hydrant water 20L / s, fire hydrant water 30L / s, fire duration 2h. Hydrant enrich the water column height 12m, hose length 20m, gun nozzle flow 5.7L / s, fire standpipe diameter is DN100. In the attic is provided a test fire hydrant, fire hydrant box each have a remote start the fire pump buttons.

The building wet automatic sprinkler system, sprinkler system design flow 40L / s. Alarm valve located in the pump room floor, set end water means the end of each wet alarm system, the other layers are set test valve and signal valve, which signals are sent to the fire control center for processing. The initial selection of 18 m3 storage tank fire 10min fire sprinkler system, fire hydrant system, water, initial fire extinguishing water from the tank, the latter by a basement fire extinguishing pumps and spray pumps water supply.

Keyword: water-supply system、drainage system、hydrant system、automatic sprinkler system、rainwater system

南京南方宾馆大楼给排水设计

一、工程概况

本工程为南京南方宾馆大楼给排水设计,主体建筑为13层宾馆(架空层一层),其它两栋建筑分别为附属用房A(7层)和附属用房B(6层),总建筑面积为11279.16m2 宾馆建筑面积为5484.4m2 附属用房面积为5404.5m2 。宾馆建筑总高度为45.0m,附属用房A建筑总高度为25.5m,附属用房B建筑总高度为21.9。宾馆建筑地下一层为消防、生活水池和杂物室;其余均为客房。附属用房A一层为商铺,二层为餐厅,三层为会议室,四、六、七层为办公室、五层为酒吧和茶室。附属用房B一层为库房,二层为商铺,三层~六层为商务办公。

(1)给水

本建筑以城市给水管网作为水源,建筑的北侧、南侧50M处分别有一市政给水管道经过,供水水压为0.25MPa。

(2) 排水

建筑采用合流排水体制,污水经过化粪池而后排入排水管网。

二、设计依据

1.建筑给水排水设计规范GBJ50015-2003(2009年版);

2.建筑设计防火规范GB50016-2006(2006年版);

3.高层民用建筑设计防火规范GB50045-95(2005版);

4.给排水制图标准GB/T50106-2001

5.自动喷水灭火系统设计规范GB50084-2001(2005版);

三、设计内容

本设计应包括生活给水系统、消防系统(包括消火栓系统和自动喷水灭火系统)、生活排水系统、雨水系统。

四、完成的工作量

  1. 设计计算说明书一本,包括如下内容:

(1)方案的选择和比较;

(2)给水系统水力计算;

(3)排水系统水力计算;

(4)消火栓系统水力计算;

(5)自动喷水灭火系统水力计算;

(6)主要设备的选型与计算

(7)格式:封面,目录,英文摘要,中文摘要,正文,参考文献。

  1. 图纸

(1) 图纸目录 1 张

(2) 给排水设计及施工说明 1 张

请支付后下载全文,论文总字数:38194字

您需要先支付 50元 才能查看全部内容!立即支付

微信号:bysjorg

Copyright © 2010-2022 毕业论文网 站点地图